1. foot
2. extinguisher
3. extinction arm
4. flexible hose
5. counterweight
6. fuse
7. conductors
8. nozzle
INSTALLATION AND FUNCTIONING
An extinguisher of 12kg (2) is placed
on the foot (1). This foot is fixed on
the ground by means of 4 bolts.
The extinction arm (3) must be
connected to the foot and is
adjustable in height (minimum height
: 130cm, maximum height : 170cm).
The flexible hose (4) is connected to
both the extinction arm and the
extinguisher.
The counterweight (5) must be
adjusted in function of the height of
the arm.
In case of a fire, the fuse (6) will melt
at a temperature of 72°C, and
release the counterweight.
By means of the conductors (7), it
falls on the percussion head of the
extinguisher. The CO2 gaz will push
the powder into the extinction arm (3)
towards the brass nozzle (8), which
will spread the powder directly on the
fire.
Options :
* second nozzle
* micro-switch
(stops fuel flow)
type |
12 kg |
contents |
12 kg |
weight |
25 kg |
powder |
BC |
height |
max 170 cm
min 130 cm |
width |
voet 22,5 cm |
length |
voet 28,5 cm |